ProductWiki.aiby PriceQ
HoneywellBurner flame detectorRead on honeywell.comSearched on PriceQ

Minipeeper Ultraviolet Flame Detector

Last updated Nov 1, 2026 · 3 entries in Page history

The Honeywell C7027A1049 Minipeeper detects the ultraviolet radiation of combustion flames and works with Honeywell flame safeguard controls on gas, oil, or combination gas-oil burners.

Part number or model
C7027A1049
Catalog number
Not assigned yet
No confirmed photo of this model

Specifications

20 fields, as the sources state them

APPLICATION

Application
The C7027A, C7035A, C7044A and C7927A Minipeeper® Ultraviolet Flame Detectors detect the ultraviolet radiation emitted by combustion flames. The flame detectors are used with Honeywell flame safeguard controls to provide flame supervision for gas, oil, or combination gas-oil burners.1

FEATURES

Features
C7027A, C7035A, and C7044A Flame Detectors are used with RA890G devices or R7249A, R7290A, R7749B and R7849A,B Amplifiers and the appropriate Honeywell controls. C7027A/C7927A has an integral collar threaded (internal 1/2-14 NPSM) for mounting on a one-half-inch sight pipe. Properly installed, the C7027A, C7035A and C7927 are pressure rated for 5 psi. Two C7027A, C7035A or C7044A Flame Detectors can be wired in parallel for difficult flame sighting installations. C7927A1016, C7027A1049, C7027A1064, C7027A1072 come with 1/2-in. spud connection for electrical wiring.1

C7027A Minipeeper® Ultraviolet Flame Detector

Ambient Operating Temperature Ratings
0°F to 215°F (-18°C to 102°C), or -40°F to 215°F (-40°C to +102°C), depending on model.1
Maximum Pressure Rating
5 psi (34.5 kPa).1
Mounting
Collar with 1/2-14 NPSM internal threads for mounting on a 1/2 in. sight pipe.1
Wiring Connections
Two 8 ft (2.44 m), color-coded, Plastic-insulated, 18 AWG, NEC Class 1 lead wires, rated for 221°F (105°C). (C7027A1064 has 24 ft [7.32 m] lead wires.) Rear of detector has a clamp type connector for 1/2 in. flexible metallic conduit. (Models are available with 1/2 in. internally threaded spud connector instead of the clamp). C7027A1114 has 44 in. (1.118 m) lead wires and 22 in. (558 mm) flexible conduit.1
Dimensions
See Fig. 1.1
NOTE
The ultraviolet radiation sensing tube is not field replaceable.1
Accessory
136733 Heat Block, laminated plastic, insulating the flame detector from sight pipe temperatures up to 266°F (130°C), 1/2-14 NPSM external threads on one end and 1/2-14 NPSM internal threads on the other end (see Fig. 7). Included with C7027A1080. 390427B Bushing, for mounting to 3/8 in. sight pipe. Included with C7027A1080.1

SPECIFICATIONS

Fig. 1. Installation dimensions of C7027A in inches (mm).
4 (102) 3-1/2 (89) 1-1/16 (27)1

C7027A, C7035A AND C7044

Approvals
Underwriters Laboratories Inc. listed: File No. MP268. Canadian Standards Association certified: Master Report LR 95329-1. Factory Mutual approved. Swiss Re (formerly Industrial Risk Insurers) acceptable. DIN approved models: C7027A1056, C7035A1049, C7035A1064.1
General Accessories
118367A Swivel Mount; provides adjustable positioning of the Flame Detectors. 105172C Seal off adapter, 3/4 in. NPT.1

INSTALLATION

IMPORTANT
The C7027, C7035, and C7044 ultraviolet radiation sensing tubes have a life expectancy of 40,000 hours of continuous use within the flame detector's specified ambient temperature and voltage ratings. When an ultraviolet radiation sensing tube wears out, the UV sensor will fail to properly discriminate between flame conditions. The C7027A, C7035A, C7044A and C7927 Flame Detectors should only be used on burners that cycle on/off or, in the absence of cycling, are periodically checked for proper operation following the application instructions provided by the equipment manufacturer.1
WARNING
The C7027A, C7035A, C7044A and C7927 Flame Detectors must be used with Honeywell flame safeguard controls (primaries, programmers, and burner management systems). Using with controls not manufactured by Honeywell could result in unsafe conditions.1

Table 9. C7027 AND C7044 ULTRAVIOLET FLAME DETECTOR CROSS REFERENCE

Current Replacement
C7027A10492
Mounting Pipe Size NPT (in.)
1/22
Lead Length (ft./in.)
8/962
Ambient Temp °F
0 to 2152
Comments
With 1/2 in. NPT connector.2

Overview

Overview
C7027, C7035 'MiniPeeper' Ultraviolet Flame Sensor Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames. Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications. Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls UL/CSA approved for USA AGA approved for Australia Only for intermittent operation. The burner has to recycle at least once per 24 hours. Features & Benefits: Rugged, compact, with encapsulated sensing tube for maximum protection Quick and easy installation on standard sight pipe3

Sources: honeywell.com, Product Data 60-2026-16, Application, Features, the C7027A section, Fig. 1, read Nov 1, 2026 UTC; honeywell.com, The Firing Line, Honeywell Flame Sensors Cross Reference, Table 9, read Nov 1, 2026 UTC; process.honeywell.com, C7027, C7035 family page, Overview text only, read Nov 1, 2026 UTC.

Size and weight

Inches and pounds, millimetres and kilograms

The product

WhatInches and poundsMillimetres and kilograms
DimensionsInstallation dimensions4×3-1/2×1-1/16 in102×89×27 mm

Figures in black are the maker’s. Figures in grey are converted by the wiki (1 in = 25.4 mm, 1 lb = 0.45359237 kg).

More from Honeywell

4 pages on the wiki

Documents

2 linked, none copied here

References

3 sources, each with the day it was read

  1. honeywell.com, Product Data 60-2026-16, Application, Features, the C7027A section, Fig. 1, read Nov 1, 2026 UTC. Supports 14 specifications, the related products, the documents
  2. honeywell.com, The Firing Line, Honeywell Flame Sensors Cross Reference, Table 9, read Nov 1, 2026 UTC. Supports 5 specifications, the related products, the documents
  3. process.honeywell.com, C7027, C7035 family page, Overview text only, read Nov 1, 2026 UTC. Supports 1 specification

Page history

Every read and every change to this page, newest first

  1. Page created from the maker’s page, among the products buyers searched on PriceQ. Product type proposed. Descriptions written at three lengths from the specifications.Claude Opus (AI agent) · Not reviewed yet
  2. Read on honeywell.com: Product Data 60-2026-16, Application, Features, the C7027A section, Fig. 1; The Firing Line, Honeywell Flame Sensors Cross Reference, Table 9.Claude Opus (AI agent) · Not reviewed yet
  3. Read on process.honeywell.com: C7027, C7035 family page, Overview text only.Claude Opus (AI agent) · Not reviewed yet

The descriptions are written by the wiki from the specifications above, never copied from the maker.

Live prices · PriceQ

What sellers ask for the Honeywell C7027A1049 today.

The wiki holds what the maker publishes. PriceQ looks up the sellers. The button opens it with this product already filled in.